Specifications
900-0161-01-00 Rev A 65
The
Grid Interface Protection
settings are adjustable. However, this is only available to operators with
installer-level access. The reason for this limitation is that there are firm rules concerning the
acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay
when exporting power back to the utility. The rules differ in different locations around the world,
although generally it is expected that the settings cannot be altered by the end user. For this reason,
the installer password must be changed from the default to get access to these settings.
Once this password has been changed, the
Grid Interface Protection
settings can be accessed by
using the installer password.
See the
Grid Tied
mode on page 15 for more information. Also see
Default Settings and Ranges
.
Firmware Revision
This manual applies to inverter models GS8048A and GS4048A with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the
OutBack website www.outbackpower.com. See page 12.
Default Settings and Ranges
NOTES:
Certain items are retained at the present setting even when the inverter is reset to factory
defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:
Table 16 Radian Inverter Settings
Field Item Default Minimum Maximum
INVERTER
Hot Key Inverter Mode
Off On, Off, or Search
CHARGER
Hot Key Charger Control On On or Off
AC Input
Hot Key
AC Input Mode
Use
Drop
or
Use
Search
Sensitivity (see page 23 for increments)
10 0 250
Pulse Length
8 AC Cycles 4 AC Cycles 20 AC Cycles
Pulse Spacing
60 AC Cycles 4 AC Cycles 120 AC Cycles
AC Input and
Current Limit
Input Priority Grid Grid or Gen
Grid Input AC Limit
50 Aac 5 Aac 55 Aac
Gen Input AC Limit
50 Aac 5 Aac 55 Aac
Charger AC Limit
GS8048A 30 Aac 0 Aac 30 Aac
GS4048A
15 Aac
0 Aac
15 Aac
Grid AC Input
Mode and Limits
Input Mode Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
108 Vac 85 Vac 110 Vac
(Voltage Limit) Upper
132 Vac 125 Vac 140 Vac
Transfer Delay
1.0 second 0.12 seconds 4.0 seconds
Connect Delay
0.2 minutes 0.2 minutes 25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc 44.0 Vdc 64.0 Vdc
(Connect) Delay
10 minutes 2 minutes 200 minutes
If Grid Zero mode
is selected:
DoD Volts
48.0 Vdc 44.0 Vdc 64.0 Vdc
DoD
Amps
GS8048A
5 Aac 1 Aac 30 Aac
GS4048A
5 Aac 1 Aac 15 Aac