Radian Series Inverter/Charger GS8048A GS4048A Operator’s Manual

Strona 2

Introduction 8 900-0161-01-00 Rev A Inverter Controls The Radian inverter has no external controls. It can operate normally without an external c

Strona 3 - Table of Contents

900-0161-01-00 Rev A 9 Commissioning Functional Test WARNING: Shock Hazard and Equipment Damage The inverter cover must be removed to perform th

Strona 4

Commissioning 10 900-0161-01-00 Rev A Figure 3 AC Test Points 2. If a system display is present, perform all programming for all functions. Th

Strona 5 - List of Figures

Commissioning 900-0161-01-00 Rev A 11 4. Using a DVM or voltmeter, verify 120 Vac (or appropriate voltage) between the master inverter’s “L1” and “

Strona 6

Commissioning 12 900-0161-01-00 Rev A Firmware Updates IMPORTANT: All inverters will shut down during firmware updates. If loads need to b

Strona 7 - Introduction

900-0161-01-00 Rev A 13 Operation Inverter Functionality The inverter is capable of being used for many applications. Some of the inverter’s opera

Strona 8

Operation 14 900-0161-01-00 Rev A requirements of the Radian inverter and the selected input mode. If necessary, the Gen terminals can accept grid

Strona 9 - Inverter Functions

Operation 900-0161-01-00 Rev A 15 BENEFITS:  Large inverter loads can be powered while staying connected to the AC input, even if the input is li

Strona 10 - Inverter Controls

Operation 16 900-0161-01-00 Rev A BENEFITS: Excess power is returned to the utility grid.  The inverter will offset the loads with excess renewab

Strona 11 - Commissioning

Operation 900-0161-01-00 Rev A 17 ∼ Before operating in Grid Tied mode, contact the utility company that provides power to the installation. They

Strona 12

About OutBack Power Technologies OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sin

Strona 13 - Adding New Devices

Operation 18 900-0161-01-00 Rev A Mini Grid In Mini Grid mode, the Radian inverter automatically rejects an AC source and runs solely from batt

Strona 14 - Firmware Updates

Operation 900-0161-01-00 Rev A 19 ∼ HBX can be combined with the settings of any other input mode (Generator, UPS, etc.). The Mini Grid input mode

Strona 15 - Operation

Operation 20 900-0161-01-00 Rev A Table 1 Summary of Input Modes Mode Summary Benefits Cautions Intended Charger Generator Accepts power from

Strona 16 - Support

Operation 900-0161-01-00 Rev A 21 Description of Inverter Operations The items in this section are operations common to all Radian inverters. These

Strona 17 - Grid Tied

Operation 22 900-0161-01-00 Rev A The following items will affect the inverter’s operation. These are only used when the inverter is generating AC

Strona 18

Operation 900-0161-01-00 Rev A 23 Search An automated search circuit is available to minimize the power draw when no loads are present. When e

Strona 19 - Backup

Operation 24 900-0161-01-00 Rev A AC Current Settings The AC current settings, Grid Input AC Limit and Gen Input AC Limit, control the amount of c

Strona 20 - Mini Grid

Operation 900-0161-01-00 Rev A 25 Gen AC Input Mode and Limits). The settings are titled Voltage Limit Lower and Upper. When adjusted, they apply

Strona 21 - in Grid Zero mode is

Operation 26 900-0161-01-00 Rev A The relay contacts are limited to 50 amps per phase or leg. The continuous loads on that output should never exce

Strona 22

Operation 900-0161-01-00 Rev A 27 Battery Charging IMPORTANT: Battery charger settings need to be correct for a given battery type. Always foll

Strona 23 - Inverting

900-0161-01-00 Rev A 1 Table of Contents Introduction ...

Strona 24 - AC Frequency

Operation 28 900-0161-01-00 Rev A between steps are marked with vertical dotted lines. A circle indicates that the inverter has begun charging to

Strona 25 - Input

Operation 900-0161-01-00 Rev A 29 Charging Steps The following items describe the operation and intended use for each individual charging step as

Strona 26 - AC Source Acceptance

Operation 30 900-0161-01-00 Rev A battery voltage (up to the maximum Absorption limit). The counter adds more time to the Absorption period wheneve

Strona 27 - Transfer

Operation 900-0161-01-00 Rev A 31 NOTE: The Float timer begins running any time the battery voltage exceeds the Float Voltage set point. This usua

Strona 28

Operation 32 900-0161-01-00 Rev A The remaining charging steps will proceed as described on the previous pages. Figure 6 Repeated Charging Cycles

Strona 29 - Battery Charging

Operation 900-0161-01-00 Rev A 33  When Cycle 4 begins, the charger proceeds through the Bulk stage and then the Absorption stage. (The space betw

Strona 30 - Charging Graphs

Operation 34 900-0161-01-00 Rev A The Radian inverter, when equipped with the Remote Temperature Sensor (RTS) will compensate for changes in tempera

Strona 31 - Charging Steps

Operation 900-0161-01-00 Rev A 35 Offset This operation is designed to use excess battery energy to power the loads when an AC source is

Strona 32

Operation 36 900-0161-01-00 Rev A Multiple-Inverter Installations (Stacking) Multiple inverters in a single system can support larger loads than

Strona 33 - New Charging Cycle

Operation 900-0161-01-00 Rev A 37 without being stacked as long as it is wired independently.  The GS8048A can be parallel-stacked with the GS4048A

Strona 34

Table of Contents 2 900-0161-01-00 Rev A Parallel Stacking (Dual-Stack and Larger) ...

Strona 35 - Equalization

Operation 38 900-0161-01-00 Rev A Power Save Each inverter consumes approximately 30 watts of idle power while it remains on, even if it is not act

Strona 36

Operation 900-0161-01-00 Rev A 39 depending on the inverter’s stacking designation.  Master Power Save Level appears on an inverter which is set

Strona 37 - Offset

Operation 40 900-0161-01-00 Rev A Additional Notes for the Radian GS8048A The GS8048A has two modules. The modules are controlled individually. Th

Strona 38

Operation 900-0161-01-00 Rev A 41 Table 4 Changing Master Power Save Levels (GS8048A) Master Slave 1 Slave 2 Slave 3 Power Save Module1 Module 2

Strona 39

Operation 42 900-0161-01-00 Rev A output voltage drops below a specific AC voltage for more than 3 seconds. This voltage limit is 30 volts below th

Strona 40 - Power Save

Operation 900-0161-01-00 Rev A 43  Cool Fan activates the AUX output when the inverter reaches a high internal temperature. It is intended to trig

Strona 41

Operation 44 900-0161-01-00 Rev A Note that even if every function in the menu is set to Off, external programming from other devices may still acti

Strona 42

Operation 900-0161-01-00 Rev A 45 System Display-Based Functions A system display such as the OutBack MATE3 can provide functions not available in t

Strona 43 - Auxiliary Terminals

Operation 46 900-0161-01-00 Rev A HBX mode has similar priorities to the Mini Grid input mode contained within the Radian inverter. Either mode may

Strona 44

900-0161-01-00 Rev A 47 Metering MATE3 Screens The MATE3 system display can monitor the GS inverter and other networked OutBack devices. From th

Strona 45

Table of Contents 900-0161-01-00 Rev A 3 List of Tables Table 1 Summary of Input Modes ...

Strona 46

Metering 48 900-0161-01-00 Rev A  Charge displays the kilowatts and AC amperage consumed for the inverter to charge the battery bank. This line al

Strona 47 - Grid Functions

900-0161-01-00 Rev A 49 Troubleshooting Basic Troubleshooting Table 6 is organized in order of common symptoms, with a series of possible causes.

Strona 48 - Load Grid Transfer

Troubleshooting 50 900-0161-01-00 Rev A Table 6 Troubleshooting Symptom Possible Cause Possible Remedy Inverter set to Search (Search mode). MATE3

Strona 49 - Metering

Troubleshooting 900-0161-01-00 Rev A 51 Table 6 Troubleshooting Symptom Possible Cause Possible Remedy Conflicting AC sources. Priority input is

Strona 50 - Battery Screen

Troubleshooting 52 900-0161-01-00 Rev A Table 6 Troubleshooting Symptom Possible Cause Possible Remedy Reduced power sold to the utility grid. AC

Strona 51 - Troubleshooting

Troubleshooting 900-0161-01-00 Rev A 53 Table 6 Troubleshooting Symptom Possible Cause Possible Remedy Loads sensitive to inverter’s transfer time

Strona 52

Troubleshooting 54 900-0161-01-00 Rev A Table 6 Troubleshooting Symptom Possible Cause Possible Remedy Generator, external fan, etc. fails to star

Strona 53

Troubleshooting 900-0161-01-00 Rev A 55 Error Messages An error is caused by a critical fault. In most cases when this occurs, the unit will shut

Strona 54 - on the

Troubleshooting 56 900-0161-01-00 Rev A Warning Messages A warning message is caused by a non-critical fault. When this occurs, the unit will n

Strona 55

Troubleshooting 900-0161-01-00 Rev A 57 Table 8 Warning Troubleshooting Message Definition Possible Remedy Fan Failure The inverter’s internal coo

Strona 56 - Module Select

Table of Contents 4 900-0161-01-00 Rev A This page intentionally left blank.

Strona 57 - Error Messages

Troubleshooting 58 900-0161-01-00 Rev A Disconnect Messages Disconnect messages explain why the inverter has disconnected from an AC source after

Strona 58 - Warning Messages

Troubleshooting 900-0161-01-00 Rev A 59 Sell Status Sell Status messages describe conditions relating to the inverter’s grid-interactive mode. Thi

Strona 59 - Temperature Events

Troubleshooting 60 900-0161-01-00 Rev A NOTES:

Strona 60 - Disconnect Messages

900-0161-01-00 Rev A 61 Specifications Electrical Specifications NOTE: Items qualified with “default” can be manually changed using the system di

Strona 61 - Sell Status

Specifications 62 900-0161-01-00 Rev A Table 12 Electrical Specifications for Radian Models Specification GS8048A GS4048A DC Input Power (contin

Strona 62

Specifications 900-0161-01-00 Rev A 63 Temperature Derating All Radian inverters can deliver their full rated wattage at temperatures up to 25°C (

Strona 63 - Specifications

Specifications 64 900-0161-01-00 Rev A FCC Information to the User This equipment has been tested and found to comply with the limits for a Class

Strona 64 - Environmental Specifications

Specifications 900-0161-01-00 Rev A 65 The Grid Interface Protection settings are adjustable. However, this is only available to operators with ins

Strona 65 - Regulatory Specifications

Specifications 66 900-0161-01-00 Rev A Table 16 Radian Inverter Settings Field Item Default Minimum Maximum Gen AC Input Mode and Limits Input

Strona 66 - Specification Compliance

Specifications 900-0161-01-00 Rev A 67 Table 16 Radian Inverter Settings Field Item Default Minimum Maximum (Gen Alert) OFF: Batt > 56.0 Vdc

Strona 67 - Default Settings and Ranges

900-0161-01-00 Rev A 5 Introduction Audience This manual provides instructions for setup and operation of the product. It does not cover instal

Strona 68

Specifications 68 900-0161-01-00 Rev A Definitions The following is a list of initials, terms, and definitions used in conjunction with this produc

Strona 69

900-0161-01-00 Rev A 69 Index 1 12V AUX ... 41 A Absorption Stage ...

Strona 70 - Definitions

Index 70 900-0161-01-00 Rev A Grid-Interactive ... 15, 68 GT Limits ...

Strona 71 - 900-0161-01-00 Rev A 69

Index 900-0161-01-00 Rev A 71 V Vent Fan Control ... 42 W Warning Symbol ...

Strona 72 - 900-0161-01-00 Rev A

900-0161-01-00 Rev A This page intentionally left blank.

Strona 73 - 900-0161-01-00 Rev A 71

This page intentionally left blank.

Strona 74

900-0161-01-00 Rev A Masters of the Off-Grid.™ First Choice for the New Grid. Corporate Headquarters 17825 –

Strona 75

Introduction 6 900-0161-01-00 Rev A Welcome to OutBack Power Technologies Thank you for purchasing the OutBack Radian Series Inverter/Charger. I

Strona 76

Introduction 900-0161-01-00 Rev A 7 Inverter Functions  Battery-to-AC inverting which delivers power to run backup loads and other functions ∼ Pro